Terminal block connections, recommended practice

From Sensoray Technical Wiki
Revision as of 09:56, 10 March 2022 by JL (Talk | contribs)

Jump to: navigation, search

The following recommendations apply to spring and screw cage terminal blocks (TBs).


Contents

Strain relief

It is recommended to secure all wires with strain reliefs. This is especially important if the wires will be subjected to vibration or pulling forces.

Wire ferrules

Wire ferrules are recommended to prevent contact loss due to oxidation and wire deformation and, in the case of stranded wire, to avoid shorts caused by splayed or broken strands.

When choosing a ferrule, ensure that its:

  • Inside diameter is large enough to accommodate the wire.
  • Outside diameter is not too large to fit into the TB.

A crimping tool is used to secure the wire to the ferrule. Always use the proper tool, which will:

  • Crimp without damaging the ferrule or wire.
  • Leave a textured surface that is readily gripped by the terminal.

To assemble:

  1. Insert the wire (or wires, in the case of a twin ferrule) into the ferrule and crimp.
  2. Insert the ferrule into the TB and tighten it in place.

Stranded wire

  • Do not insert bare strands directly into the TB.
  • Do not apply solder to the strands.
  • Always use a wire ferrule.

Solid wire

  • The use of a wire ferrule is optional.
  • It may be acceptable to insert bare wire into the TB. This should be avoided if the wire is subjected to vibration or pulling forces, or if the wire would be significantly deformed by the compressive force of the TB jaws.
  • Do not flex the wire after installation.